Depending on your preference, either Metric or Imperial values may be used to calculate the number of tubes required. Please note: 1 kWh/m2/day = 317.1 Btu/ft2/day
*Water Volume = This should represent the actual volume of hot water used at the tap in total each day.
Although most hot water systems have target temps of 60oC / 140oF, when showering a temperature of between 42oC / 107oF and 45oC / 113oF is normally used. Therefore 300L of hot water at the tap may only draw 220L of hot water (at 60oC / 140oF) from the storage tank.
**Temperature Rise = target tap hot water temp - average mains cold water temp.
Target hot water temp should usually be around 42oC / 107oF to 45oC / 113oF
Cold water usually fluctuates by about 10oC / 18oF between winter and summer. A check of your local weather records should provide you with an idea of average cold water temperatures (normall about 10oC / 50oF in winter and 20oC / 68oF in summer, in mild regions).
Apart from the three key factors used in the calculation above, you may also need to consider:
1. Annually/daily shade patterns
2. Angle/direction of installation (a less than ideal angle will reduce efficiency)
6. Installation site (Do you have enough room for the collector(s)?)
The estimations above are just a guide and are based on a average summer performance level of 70%. As explained above it is best not to oversize the system. Your local distributor may need to complete a onsite inspection to accurately assess your requirements and design a solar water heating system which suits your needs. For more information about performance and heat energy output please
|